D.c. link and fan cabinet components – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 344

Advertising
background image

6-54

Component Definition and Maintenance

7000-UM150I-EN-P – June 2013

7000 “B” Frame

D.C. Link and Fan Cabinet Components

AC/AC

Converters

3-phase

fan power

transformer

Ground Bus

“Hold up” Capacitor

DC Link Inductor
(Barrier removed)

Fan Power Cable
Entry (bottom)

Impeller Access
Panel

Fan

Inlet Ring

Figure 6.40 – DC Link and Fan cabinet

with control panel shown

Figure 6.41 – DC Link and Fan Cabinet

with fan control panel removed


The door of the cabinet is interlocked such that it cannot be opened
unless the fan power is disconnected. The fan power disconnect
handle is mounted on the right-hand side of the cabinet.


When the door is opened, fan control components are accessible.
Behind the fixed fan control panels is the medium voltage
compartment where the DC link and fan are located.


The D.C. link is mounted on the floor plate of the cabinet. Airflow
barriers are assembled around the coils of the inductor to direct a
portion of the cooling air through the inductor.


Power connections are made to the inductor via its flexible leads.
There are four power connection points labeled L+, L-, M+, and M-.


The iron core of the D.C. link is equipped with thermal protection.