Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 472

Advertising
background image

7-50

Troubleshooting

7000-UM150I-EN-P – June 2013

7000 “B” Frame

WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

2U1A Offline SC

300

6P SCR RECTIFIER WARNING

(Offline Short-Circuit)
FOR REDUNDANT DEVICE CAPABILITY
ONLY

For SCR rectifiers, this warning will occur
after the initial contact closure, or during the

diagnostic sequence after a start command.
This is the first test on the rectifier. When all
devices blocking, the feedback from the

devices should toggle from open to short to
open every time the line voltage sine wave

passes through zero. If this is consistently
showing short (no feedback), then the drive
assumes that the device is Short-Circuited.

– Complete a resistance check on the

rectifier, including the gate-cathode
resistance, the snubber and sharing
resistors

– Complete a firing check on the rectifier
– Verify the snubber circuitry, and the

sharing resistors

– Verify fiber optic integrity from SCRGD

board transmitter to FOI board receiver

– Replace all faulty components

– NOTE: There is only the Redundant

option available on the Rectifier, and only
on 6P drives (SCR orPWM). You can
not have N-1 operation on the rectifier
since we can not control the line voltage.

2U1B Offline SC

306

2U1C Offline SC

318

2U4A Offline SC

303

2U4B Offline SC

309

2U4C Offline SC

321

2V3A Offline SC

302

2V3B Offline SC

308

2V3C Offline SC

320

2V6A Offline SC

305

2V6B Offline SC

311

2V6C Offline SC

323

2W2A Offline SC

301

2W2B Offline SC

307

2W2C Offline SC

319

2W5A Offline SC

304

2W5B Offline SC

310

2W5C Offline SC

322

2U1A Online SC

288

6P SCR RECTIFIER WARNING

(Online Short-Circuit)
FOR REDUNDANT DEVICE CAPABILITY
ONLY

For SCR rectifiers, this warning will occur

during operation. Before an individual leg is
fired, the drive takes 5 samples of the
voltage across that device. This is because

the notching on the line could cause
individual readings to be low. If they are all

low, the device is assumed to be short-
circuited and a warning occurs. There is
also a parameter called Rectifier Device

Diagnostic Delay (P266), which allows you
to change the number of consecutive firings
to eliminate nuisance warnings. It will still

check 5 times before each firing, but will
now require the condition to exist for the

number of consecutive firings set in the
Diagnostic Delay parameter for a warning to
occur.

– For multiple device faults, the risk of a

line to line short exists, so tests with MV
isolated should be attempted

– Complete a resistance check on the

rectifier, including the gate-cathode
resistance, the snubber and sharing
resistors

– Complete a firing check on the rectifier
– Verify the snubber circuitry, and the

sharing resistors

– Verify fiber optic integrity from SCRGD

board transmitter to FOI board receiver

– Replace all faulty components
– For nuisance faults, contact the factory

about extending the Diagnostic Delay

– NOTE: There is only the Redundant

option available on the Rectifier, and
only on 6P drives (SCR orPWM). You
can not have N-1 operation on the
rectifier since we can not control the line
voltage.

2U1B Online SC

294

2U1C Online SC

312

2U4A Online SC

291

2U4B Online SC

297

2U4C Online SC

315

2V3A Online SC

290

2V3B Online SC

296

2V3C Online SC

314

2V6A Online SC

293

2V6B Online SC

299

2V6C Online SC

317

2W2A Online SC

289

2W2B Online SC

295

2W2C Online SC

313

2W5A Online SC

292

2W5B Online SC

298

2W5C Online SC

316