Component Definition and Maintenance 6-33

7000 “B” Frame

7000-UM150I-EN-P – June 2013

12. While grounded, use a long Phillips screwdriver to remove the 2

screws that hold the SCR SPGD Board to the metal bracket on
the red glastic assembly. Retain the hardware.

13. Pull the 4 plastic clips that secure the SCR SPGD Board to the

glastic assembly. Retain the hardware.

14. Install the new SCR SPGD Board in the assembly with the 4 plastic

clips and use the screws to secure the board to the metal bracket.

15. Clean the heatsink with a soft cloth and rubbing alcohol.

16. Slide the SCR and SCRGD Board back into place until the

mounting bracket makes contact with the heatsink. Use the
Phillips screwdriver to tighten the assembly to the heatsink.

17. Reapply the clamping load as described in „Uniform Clamping

Pressure‟ above.

18. Connect the control power cable and the fiber optic cables,

ensuring that the bend radius is not exceeded.