Commissioning 4-53

7000 “B” Frame

7000-UM150I-EN-P – June 2013

System Test

Prior to applying medium voltage, it is necessary to verify the entire
low voltage control circuit to ensure the drive operates as desired.
Failure to perform this test may result in damage to the drive or
process in the event that the control does not operate as expected. This
section of the manual provides instruction for the following five tests:

• System Test Mode

• Start/Stop Contactor Control

• Status Indicators

• Analog I/O

• Configurable Alarms

System Test Mode

The following procedure explains how to enter System Test Mode.
This allows the drive to operate the drive‟s low voltage control
circuit without medium voltage present.


Drive status I/O will be active while performing tests in System Test
Mode. If the drive I/O is monitored remotely, process control should
be notified in advance to avoid confusion.

A T T E N T I O N

A T T E N T I O N

Ensure that the drive is isolated from medium
voltage prior to starting this test.



Ensure you have Advanced access.

Now, from the main screen, press
SETUP [F8] to get to Parameters,
and then Enter. You should be on
Feature Select, the first group.