Troubleshooting

7-9

7000 “B” Frame

7000-UM150I-EN-P – June 2013

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

will appear if the specific input (1-16) is
configured in Fault Config as a Class 1 or

Class 2 fault.

– Verify voltage signals from external

sources

Ext Cooling Loss

(C-Frame only)

224

The drive has detected the loss of the ability
to provide cooling for the drive. This is

detected through feedback from the Heat
Exchanger Cooling fans contactors and

overloads.

– Review the inputs to the drive Liquid

Cooling XIO and determine the source of

the missing signals

– Investigate the Heat Exchanger fans and

control for a cause

Field Loss

35

This fault indicates that the field current is
either missing or insufficient. This is done

through an indirect method by checking if
the drive is in Flux Regulator limit for the
delay set in Field Loss Delay (P559). This
means your exciter reference I Field
Command (P314) is at 100% for the time of
the delay.

– Verify the field current from the exciter is

present

– Verify the analog output from the drive is

reaching the field exciter control circuit

Gate Test Pwr On

196

The temporary power supply harness used
for Gating Tests on the SCR rectifiers has

not been removed from the DC/DC Power
Supply, and you have attempted to start the
drive.

– Remove the test harness from the drive

immediately after Gate Test is finished

– Verify fault detection wiring is per the

drawings, and measure the voltage on the

trip signals back to the CIB. The 5VDC is

supplied from the CIB to the fault circuit,

and is pulled low on the power supply

when healthy.

– Replace the DC/DC Power Supply if the

harness is removed and the fault can not

be cleared

GND Offset

245

CIB Hardware Fault

– CIB Hardware Problem
– Cycle control Power to the drive, and if

the problem still exists the board should
be replaced

Ground OC

173

The Ground Current measured on the
Ground Fault CT has exceeded the value in
Ground Fault Overcurrent Trip (P171) for

the duration set in Ground Fault Overcurrent
Delay (P172). The GFCT (Zero-Sequence

CT) is not installed in all drives.

– Verify the Burden resistor has not

opened

– Verify parameters are set properly
– Megger the drive and motor and input

transformer/AC line reactor to search for
a ground fault in the system

Input Prot’n #1

135

Standard External Fault/Warning Input
included to allow the end-user to install a
protective relay (IE Input Feed Protection

Relay) auxiliary contact that can activate a
drive fault or warning, depending on
configuration of InputProt1 Class (P440).

– Check device responsible for the

auxiliary contact to this input and
investigate the fault indicated by the
device‟s fault message

– Investigate internal and external causes

for this fault code

– Check the 120V signal through the

external device

– Check the XIO board inputs and

parameter status bits

InputProt’n #2

140

Standard External Fault/Warning Input
included to allow the end-user to install a

protective relay (IE Input Feed Protection
Relay) auxiliary contact that can activate a

drive fault or warning, depending on

– Check device responsible for the

auxiliary contact to this input and

investigate the fault indicated by the
device‟s fault message

– Investigate internal and external causes