Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 436

Advertising
background image

7-14

Troubleshooting

7000-UM150I-EN-P – June 2013

7000 “B” Frame

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Master CurrentUB

163

The measured and calculated phase
currents in the Master Bridge have
exceeded the value set in Line Current

Unbalance Trip (P108) for the duration set in
Line Current Unbalance Delay (P109).

– Verify that all Current Transformer

connections are connected properly and
that no wires are reversed – Ring-out

wires to verify connections

– Check grounding on CTs
– Ensure that all plugs are firmly

connected in the SCBL

– Check that all input voltages are

balanced

– Verify Parameter settings
– Check the burden resistors
– Verify the Input Capacitor values if

installed

– Verity that there are no open sharing

resistors.

– Verify all Line Thyristors are firing in

Gating Test Mode

– Check the Line Filter Capacitors (for

PWM rectifier drives). Refer to Chapter 6

of the User‟s Manual for detailed
instructions on Testing Filter Capacitors.

Master VoltageUB

160

The measured phase voltages in the Master
Bridge have exceeded the value set in Line
Voltage Unbalance Trip (P271) for the

duration set in Line Voltage Unbalance
Delay (P272).

– CHECK TSN FUSING
– Verify the VSB connections and tap

settings, and check resistance of VSB

board – Megger board to confirm integrity

– Check actual voltage values on the

Operator Interface terminal for each
bridge and the total line voltage

– Check for possible source voltage supply

problems

– Use Multimeter and Oscilloscope to

check voltages on the drive voltage test

points

Motor Current UB

33

The measured current unbalance on the
drive output has exceeded Mtr I UB Trip

(P208) for the duration set in Mtr I UB Delay
(P214).

– Verify the current sensor wiring and

Burden Resistors from the Motor current
sensors

– Verify the HCS power
– Check the Motor Filter Capacitors for

balanced loading on all 3 phases. Refer
to Chapter 6 of the User‟s Manual for

detailed instructions on Testing Filter
Capacitors.

– Investigate the possibility of Motor

winding or cabling problems

Advertising