7-18

Troubleshooting

7000-UM150I-EN-P – June 2013

7000 “B” Frame

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Mstr Xfr Err

46

Master transfer Error
This is applicable to parallel drive only

– The master drive cannot find a slave

drive able to take over as master

– Possible causes are: slave drive not

ready, or slave drive masked off

Mtr Cap OV

44

Motor filter capacitor Over Voltage fault.
This is for ESP application

– This is drive output Voltage [Surface

voltage terminology used in ESP

application]. The drive gives this fault in
an ESP application only.

– The protection uses P#181 setting but

drive calculates the motor filter cap
voltage [Surface V] which is different
from motor voltage in ESP application.

– Check the voltage sensing board for any

resistor failure

– Check for any open circuit at the drive

output.

– Check the devices at the inverter.

MV in Gate Test

26

The drive has Medium Voltage applied and
the user attempted to place the drive in
Gating Test mode.

– Check input contactor control and Status
– Ensure that the isolation switch is in the

open position and locked out – Confirm
with hot-stick and status parameters

MV in System Test

27

The drive has Medium Voltage applied and
the user attempted to place the drive in

System Test mode.

– Check input contactor control and Status
– Ensure that the isolation switch is in the

open position and locked out – Confirm

with hot-stick and status parameters

No DO/OP Ctctr

37

This fault is specifically used for Open
Circuit Test Mode, which demands that an
Output Contactor be specified in IsoSw/Ctctr

Cfg (P192). If the contactor is not specified,
you will get this fault in Open Circuit Test
Mode. This is to help avoid inexperienced

people putting the drive in open circuit test
mode without actually open circuiting the
output with either a contactor or by

disconnecting the cable.

– If there truly is no Output Contactor in the

system, then you can mask the fault.
Then there will be a No DO/OP Ctctr

warning, and you can continue with the
test.

Open Cct UV

36

Under Voltage during open circuit test

– During open circuit test mode the drive

trips on this fault if difference between
flux command base speed value and
drive output voltage is more than 40%,

and speed ramped to 95% of the line
frequency.

– Check if any short circuit at the drive

output

– Make sure motor is not connected

OutPut Open

43

DO or OP open fault

– Drive sees DO or OP contactor open.
– Check for open circuit at the drive output

PD Capcty Lo

47

Parallel Drive Capacity Low.
This is applicable to parallel drive only

– The available drive capacity is less than

50% of the motor rated current. The

drive cannot run.