7-28

Troubleshooting

7000-UM150I-EN-P – June 2013

7000 “B” Frame

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

2U1A Online OC

342

6P or 18P SCR RECTIFIER FAULT

(Online Open-Circuit)

For SCR rectifiers, this fault will occur during
operation. After a firing signal is sent to a

device, the drive monitors the feedback
status to ensure the voltage drops to zero

across that device, indicating it has been
turned on. If the feedback does not drop to
zero before approximately 30-50 µsec, the

drive will assume the device is open and a
fault will occur. There is a 6 cycle fixed
delay, which means that this has to occur for
6 consecutive firings before the fault is
instigated.

– Complete a resistance check on the

rectifier, including the gate-cathode
resistance, the snubber and sharing
resistors

– Complete a firing check on the rectifier
– Verify the snubber circuitry, and the

sharing resistors

– Verify fiber optic integrity from FOI board

transmitter to SCRGD board receiver

– Replace all faulty components

2U1B Online OC

348

2U1C Online OC

390

2U4A Online OC

345

2U4B Online OC

351

2U4C Online OC

393

2V3A Online OC

344

2V3B Online OC

350

2V3C Online OC

392

2V6A Online OC

347

2V6B Online OC

353

2V6C Online OC

395

2W2A Online OC

343

2W2B Online OC

349

2W2C Online OC

391

2W5A Online OC

346

2W5B Online OC

352

2W5C Online OC

394

3U1B Online OC

414

3U4B Online OC

417

3V3B Online OC

416

3V6B Online OC

419

3W2B Online OC

415

3W5B Online OC

418

4U1C Online OC

420

4U4C Online OC

423

4V3C Online OC

422

4V6C Online OC

425

4W2C Online OC

421

4W5C Online OC

424