Component Definition and Maintenance 6-27

7000 “B” Frame

7000-UM150I-EN-P – June 2013

2. To replace a thermal sensor, refer to page P-2 regarding

electrostatic discharge.

3. The heatsink with the thermal sensor must be removed from the

PowerCage. Remove clamp load (refer to Figure 6.19).

4. Remove the device (SGCT or SCR) that is secured to the heatsink

with the thermal sensor. (Refer to Figure 6.15., 6.16 or 6.17).

5. Disconnect the fiber optic cable to the temperature feedback board.

6. Remove two M8 screws holding the heatsink in place.

7. Remove the heatsink with the temperature feedback board from

the PowerCage.

8. Disconnect the plug that connects the thermal sensor to the

circuit board.

9. Remove the screw that attaches the thermal sensor to the heatsink.

10. Replace with the new thermal sensor and cable assembly.

11. Note there is a small voltage difference between the thermal

sensor and its heatsink. For proper function, it is essential to
mount the small insulating pad between the thermal sensor and
the heatsink and the insulating bushing between the thermal
sensor mounting screw and the thermal sensor (see Figure 6.21).

12. Replacement of the heatsink with the new thermal sensor is in

the reverse order of removal.

13. Follow procedure “Uniform Clamping Pressure” to ensure the

heatsinks are clamped to a uniform pressure.

Insulating bushing

Mounting pad

Temperature

feedback

circuit

board

Thermal sensor and

cable assembly

Mounting screw

Figure 6.21 – Replacing the Heat Sensor