Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 429

Advertising
background image

Troubleshooting

7-7

7000 “B” Frame

7000-UM150I-EN-P – June 2013

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

DC Link OC SW

171

The Measured I DC Link Feedback (P322)
has exceeded DC Overcurrent Trip (P169)
for the duration set in DC Overcurrent Delay

(P170). This fault should never occur on it‟s
own, but only after a DC Link OC HW fault.

– Setup trending to capture DC Link

Feedback and other related read-only

parameters (Contact factory if you
require assistance)

– Check Alpha Line, and verify that the

value is not too low (15

) and the current

regulator is not in limit; Decrease Flux

Command Base Speed or increase
incoming Line Voltage

– Restart the drive to allow the start up

diagnostics to detect any shorted

thyristors, but only attempt this once if
shorted SCRs are detected

DC Link OT

137

The thermal switch in the drive DC Link
Reactor has detected an over-temperature
and has opened. There is a thermal switch in

each DC Link winding, and they are
connected in series.

– Verify operating conditions (ambient/

altitude/ load levels/ ventilation and fans)
and verify that the DC Link Reactor is

within ratings

– Check the 120V signal through the

thermal switch

– Verify the drive cooling circuit is

operating correctly (Air Pressure value or

liquid-cooling path)

– Check the XIO board inputs and

parameter status bits

– Determine through elimination whether

there is a faulty switch and replace if
necessary

DC/DC Fail

155

The last of the 5VDC or the 15VDC supplies
from the DC/DC power supply to the drive
control logic has failed, or any of the other

voltages that are non-redundant have failed.
This fault means that you will have no
voltage on a required output.

– Measure the input voltage to the DC/DC

power supply and verify it is at 56VDC

– Measure the output voltage and compare

to expected values listed in Chapter 4 of

the User‟s Manual

– Verify fault detection wiring is per the

drawings, and measure the voltage on the

trip signals back to the CIB. The 5VDC is

supplied from the CIB to the fault circuit,

and is pulled low on the power supply

when healthy.

– Verify the output from the alarm signal is

wired correctly.

– If 5V DC signal from CIB is not pulled low

when connected to the DC/DC power

supply, then the power supply is the

cause. Replace the power supply.

Advertising