7-10

Troubleshooting

7000-UM150I-EN-P – June 2013

7000 “B” Frame

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

configuration of InputProt2 Class (P444).

for this fault code

– Check the 120V signal through the

external device

– Check the XIO board inputs and

parameter status bits

Input Xfmr/LR OT

136

The temperature switch in the drive Input
Isolation Transformer or Line Reactor has

detected an over-temperature and opened.
There is a thermal switch in each phase

winding, and they are connected in series.

– Verify operating conditions (ambient/

altitude/ current levels/ ventilation and

fans/ cooling oil) and verify that the
Rectifier Transformer/Reactor is within

ratings

– Check the 120V signal through the

thermal switch

– Verify that it is not a faulty switch
– Check the XIO board inputs and

parameter status bits

– Determine through elimination whether

there is a faulty switch and replace if
necessary

Inv HeatSink FO

76

While Not Running, the Fiber Optic signal
from the TFB on the Inverter Heatsink,

connected to Channel A fiber optic receiver
RX7 on FOI-M-A is not present. This is only
a fault while not running. If this occurs while

running it will appear as a warning.

– Check TFB and FOI board for power
– Check the Fiber Optic cables are

properly seated in the transmitters and

receivers

– Check the fiber optic cable for kinks,

bends, breaks that could be blocking the
signal

– This can occur if the sensor is not

connected to the TFB

Inv Temp Ch B FO

77

Not Normally Used: While Not Running, the
Fiber Optic signal from the optional TFB
connected to Channel B fiber optic receiver
RX7 on FOI-M-B is not present. This is only
a fault while not running. If this occurs while
running it will appear as a warning.

Inv HS Low Temp

40

If the measured temperature IHeatsink
Temp C (P253) is less than 2°C, and the
drive is not running, the drive will display this

fault.

– Verify that the ambient in the control

room is not below 2°C

– Verify power to the TFB
– There could be a mechanical problem

with the temperature sensor or with the
cable feeding the signal back to the TFB

– Swap with the rectifier hardware to

identify the bad component

Inv ChB Low Temp

41

If the measured temperature Temp I Ch B C
(P552) is less than 2°C, and the drive is not
running, the drive will display this fault. This

is not enabled on most drives, and the
parameter is a high-level parameter.

Inv Heatsink OT

69

The temperature detection on the Inverter
Heatsink, connected to Channel A fiber optic
receiver RX7 on FOI-M-A, has exceeded
Inverter Heatsink Temperature Trip (P315).

– Confirm actual temperature in

parameters is not higher than the trip
value – If so, investigate the conditions of
the drive (ambient/ loading/ elevation /
ventilation/ filter status /heatsink
clogging)

– Check the sensor and temperature

offline (ambient) for accuracy

Inv ChannelB OT

70

Not Normally Used - The temperature
detection on an Inverter Heatsink,

connected to fiber optic receiver RX7 on
FOI-M-B, has exceeded Inverter
Temperature Trip Channel B (P570)