4-54

Commissioning

7000-UM150I-EN-P – June 2013

7000 “B” Frame

Press Enter, and then use the down
arrow to get to Operating Mode.

Press Enter and use the down
arrow to get to System Test. Press
Enter, and you now will be in
system test mode. From this point
you can completely check the
entire system without medium
voltage. As long as you have test
power to all your contactors, you
can start, stop, E-Stop, trigger
faults, check remote IO, check
PLC inputs, and verify other
functionality.


A T T E N T I O N

A T T E N T I O N

Ensure that the drive is no longer running in
system test mode prior to applying medium
voltage to the drive line-up. Failure to do so
may result in equipment damage.