4-64

Commissioning

7000-UM150I-EN-P – June 2013

7000 “B” Frame

1. Press the Diagnostic Soft Key (DIAGS [F9]).

2. Press the Diagnostic Setup Soft Key (D_SETUP [F8]) to begin

programming the diagnostic settings.

3. Cursor the backlit section to Trace 1 and press the enter key to

begin programming. Scroll through the parameter list until
Feedback – Status Flag2 (238) is located. Select this as Trace 1.

4. Select Trace 2 through 8 as described in the step above. Note

that when you finish Trace 4, just press the down arrow and you
will get to the screen showing traces 5-8.

5. Press the TRIGGER Soft Key until the letter S appears in front

of the Trigger parameter.

6. Press the RATE Soft Key to program the trending sampling rate.

This will be set to 0 msec in this example.

7. Press the DATA Soft Key to set the trigger level for the fault.

This should be set to C.

8. Press the COND Soft Key to program the logic for the trigger level.

In this example the COND will be set as an OR condition “+”

9. Press the POST Soft Key to set up how many samples will be

recorded after the trigger. In this example the POST value will
be set to 20%. The remaining 80% of the samples will be
recorded prior to the trigger.


Once these settings have been programmed, the drive is ready to
trend. Now the drive will trend data at the next fault.

The next test required to test phase rotation requires that medium
voltage be applied to the drive input. Ensure that the drive is
thoroughly inspected for debris and tools prior to energizing the
drive. Furthermore, ensure that all protective barriers have been
re-installed before continuing. Ensure that you have taken the drive
out of System Test mode, and have returned to Normal operating
mode.