Ground filter component replacement – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 302

Advertising
background image

6-12

Component Definition and Maintenance

7000-UM150I-EN-P – June 2013

7000 “B” Frame

The number of capacitors will vary depending on the system voltage.

1. Ensure there is no power to the equipment.

A T T E N T I O N

A T T E N T I O N

To prevent electrical shock, ensure the main
power has been disconnected before working
on the capacitor. Verify that all circuits are
voltage free using a hot stick or appropriate
voltage-measuring device. Failure to do so
may result in injury or death.

2. Note the position of the leads.

3. Disconnect the leads connected to the failed capacitor/resistor

bank.

4. Loosen and remove mounting screws as indicated in Figure 6.10

and remove the failed component.

5. Assemble the new component in the reverse order of

disassembly.

6. Reattach the leads strictly adhering to the torque requirements

outlined in Figure 6.10)

I M P O R T A N T

I M P O R T A N T

The maximum torque for the capacitor terminal is
3.4 Nm (30 lb-in).

Important!

Torque on Resistor Bank Assembly
1,2 Nm (11.0 lb-in) maximum

Loosen screws to release capacitors

Remove screws for

replacing resistor bank.

Important!

Torque on capacitor terminals
3,4 Nm (30 lb-in) maximum

Figure 6.10 – Notch Filter Capacitor Resistor

Ground Filter Component

Replacement

Advertising