Troubleshooting

7-33

7000 “B” Frame

7000-UM150I-EN-P – June 2013

WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

DI Contctr Fdbk

118

This warning indicates that the drive has
sensed MV on the front end, but there is no
input contactor status coming back to the

drive

– Verify the contactor is closed
– Confirm the feedback path from the

contactor to the XIO

– Replace XIO if required

DI Contctr Open

18

The input contactor has been commanded

to close and the contactor closed feedback
has not been detected.

– Ensure the associated starter unit is set

to Normal mode

– Verify the feedback from the contactor

status (normally control relay auxiliary
and contactor mechanical auxiliary) is
wired properly and powered

– Verify that there is control power to the

contactor

– Verify the associated SCB I/O
– Verify that the Holding Coil or Closing

Coil is not shorted

– Review Contactor control wiring
– These warnings may also occur during

the autorestart feature, as the loss of
power may also result in the inability to
hold in the contactor during the outage

DI Contctr Clsd

19

The input contactor has been commanded
to open and the contactor open feedback
has not been detected.

DO Contctr Open

20

The output contactor has been commanded

to close and the contactor closed feedback
has not been detected.

DO Contctr Clsd

21

The output contactor has been commanded

to open and the contactor open feedback
has not been detected.

OP Contctr Open

46

The system output contactor has been
commanded to close and the contactor
closed feedback has not been detected.

OP Contctr Clsd

47

The system output contactor has been

commanded to open and the contactor open
feedback has not been detected.

BP Contctr Open

37

The bypass contactor has been commanded

to close and the contactor closed feedback
has not been detected.

BP Contctr Clsd

38

The bypass contactor has been commanded
to open and the contactor open feedback
has not been detected.