Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 195

Advertising
background image

4-36

Commissioning

7000-UM150I-EN-P – June 2013

7000 “B” Frame


An SCR that has failed from anode to cathode will commonly produce
a resistance value of 0 for a shorted device or

Ω for an opened

device. Unlike the SGCT, it is highly irregular for an SCR to have a
partially shorted device. If an SCR is found to be out of tolerance,
refer to Chapter 6 – Component Definition and Maintenance for
detailed instructions on how to replace the SCR assembly.


SCR Sharing Resistance Test


To test the sharing resistor of an SCR module, disconnect the 2-pole
plug of the self-powered gate driver board labeled SHARING and
SNUBBER on the circuit board. The red wire of the plug is the
sharing resistor. Measure the resistance between the red wire of the
plug and the heatsink to the left. A value of 80 k-ohms indicates a
healthy sharing resistor.

Resistance between heatsink and

red wire at plug is sharing resistance


Figure 4.9 – SCR Sharing Resistance Test

Advertising