Temperature sensing – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual
Page 316

6-26
Component Definition and Maintenance
7000-UM150I-EN-P – June 2013
7000 “B” Frame
I M P O R T A N T
I M P O R T A N T
Never rotate the lock nut located outside the
indicating washer at the end of the threaded rod.
The rotation of the outer nut will affect the torque
calibration, which is factory set. Only adjust the
inside nut. (See Figure 6.
20
.)
SGCT captive screws
Inside nut used for
loosening and applying
load to assembly
DO NOT ADJUST outside nut.
Disc springs
Clamp head block
Figure 6.20 – Detail of the clamping assembly
Temperature Sensing
Thermal sensors are located on one heatsink in the rectifier and one
heatsink in the inverter. The thermal sensors are mounted on the
heatsink with the temperature feedback circuit board.
1. Ensure there is no power to the equipment.
A T T E N T I O N
A T T E N T I O N
To prevent electrical shock, ensure the main
power has been disconnected before working on
the drive. Verify that all circuits are voltage free
using a hot stick or appropriate voltage-
measuring device. Failure to do so may result in
injury or death.