Customer interface board (cont.) – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 380

Advertising
background image

6-90

Component Definition and Maintenance

7000-UM150I-EN-P – June 2013

7000 “B” Frame



The following table illustrates the most commonly used test points.

New SCB Board

(80190-378-xx)

Old SCB Board

(80190-278-xx)

Description

TP #

Label

TP #

Label

3

VBCXFR_OUT

1

VBCXFR_OUT

Voltage BC on Line Side of Bypass Contactor, unfiltered

4

VABXFR_OUT

2

VABXFR_OUT

Voltage AB on Line Side of Bypass contactor, unfiltered

5

VAB2_OUT

3

VAB2_OUT

Voltage AB on Slave 1 input winding, unfiltered

6

VBC2_OUT

4

VBC2_OUT

Voltage BC on Slave 1 input winding, unfiltered

7

VCA2_OUT

5

VCA2_OUT

Voltage CA on Slave 1 input winding, unfiltered

8

VAB3_OUT

6

VAB3_OUT

Voltage AB on Slave 2 input winding, unfiltered

9

VBC3_OUT

7

VBC3_OUT

Voltage BC on Slave 2 input winding, unfiltered

10

VCA3_OUT

8

VCA3_OUT

Voltage CA on Slave 2 input winding, unfiltered

11

VAB1_OUT

9

VAB1_OUT

Voltage AB on Master input winding (SCBL) or Motor (SCMB), unfiltered

12

VBC1_OUT

10

VBC1_OUT

Voltage BC on Master input winding (SCBL) or Motor (SCBM), unfiltered

13

VCA1_OUT

11

VCA1_OUT

Voltage CA on Master input winding (SCBL) or Motor (SCBM), unfiltered

14

VDC_AVG

12

VDC_AVG

DC Link Average Voltage across Inverter Side (SCBL only), calculated

28

-15V

24

-15V

-15V DC Analog Power

29

AGND

25

AGND

Analog Power Common

30

+15V

26

+15V

+15V DC Analog Power

31

-24V

27

-24V

-24V DC Hall-Effect Transducer Power

32

LEMGND

28

LEMGND

Hall-Effect Transducer Power Common

33

+24V

29

+24V

+24V DC Hall-Effect Transducer Power

34

+5V

30

+5V

+5V DC Digital Power

35

DGND

31

DGND

Digital Power Common

36

VN

32

VN

Voltage from Filter Capacitor Neutral Point, unfiltered

38

VNG

35

VNG

Converter Neutral-Ground Voltage, calculated

64

IDCP

42

IDCP

DC Link Current Feedback, filtered

66

IFIELD

45

IFIELD

Synchronous Motor Field Current Feedback, filtered

74

DAC_TP1

76

DAC_TP1

Assignable Test Point (Rect_TP1 [SCBL] or INV_TP1 [SCMB] parameters)

75

DAC_TP1

77

DAC_TP1

Assignable Test Point (Rect_TP2 [SCBL] or INV_TP2 [SCMB] parameters)

1

IA1_OUT

N/A

Across R17

Current Phase A, Master Bridge, unfiltered

2

IC1_OUT

N/A

Across R29

Current Phase C, Master Bridge, unfiltered

15

IA2_OUT

N/A

Across R33

Current Phase A, Slave 1 Bridge, unfiltered

27

IC2_OUT

N/A

Across R66

Current Phase C, Slave 1 Bridge, unfiltered

40

IA3_OUT

N/A

Across R75

Current Phase A, Slave 2 Bridge (SCBL) or Motor (SCBM), unfiltered

41

IC3_OUT

N/A

Across R89

Current Phase C, Slave 2 Bridge (SCBL) or Motor (SCBM), unfiltered

62

IDCP_OUT

N/A

Across R138

DC Link Feedback Current (SCBL), unfiltered

70

IGND_OUT

N/A

Across R140

Zero Sequence Feedback Current (SCBL), unfiltered

75

IFIELD_OUT

N/A

Across R156

Field Current Feedback (SCBL), unfiltered

67

DOUT0

63

DOUT0

Digital Output command for DI Contactor (SCBL) or Bypass Contactor (SCBM)

65

DOUT1

62

DOUT1

Digital Output Command for Bypass Enable (SCBM)

60

DOUT3

69

DOUT3

Digital Output Command for DO Contactor (SCBL) or OP Contactor (SCBM)

55

DIN0

N/A

Digital Input Status for DI Contactor (SCBL) or Bypass Ctctr (SCBM)

53

DIN1

N/A

Digital Input Status for DI Isolation Switch (SCBL) or Bypass Isol. Sw. (SCBM)

50

DIN2

N/A

Digital Input Status for OP Contactor (SCBL) or OP Contactor (SCBM)

47

DIN3

N/A

Digital Input Status for OP Isolation Switch (SCBL) or OP Isol. Sw. (SCBM)

44

ENCA

N/A

Pulse Train from the Input of the Encoder Signal, Channel A

45

ENCB

N/A

Pulse Train from the Input of the Encoder Signal, Channel B

Requires the usage of isolated probes or isolation channels on the oscilloscope to avoid damaging the PF7000 Drive.

Customer Interface Board

(cont.)

Advertising