Troubleshooting

7-23

7000 “B” Frame

7000-UM150I-EN-P – June 2013

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

U1A Fbk FO Loss

93

INVERTER SGCT FAULT

(Feedback Fiber-Optic Loss)

This fault will only occur during the initial

contactor closure and the diagnostic
sequence after a start command. The

inverter monitors the state of the feedback
before a gate pulse is given, and monitors
the feedback after a gate pulse has been

sent. This fault occurs when the feedback
was low from the device before gating, and
is still low from the device after gating. The

drive then assumes the feedback must be
the problem.

The firmware now completes a diagnostics

sequence immediately after any drive reset,
with the goal of detecting faults before any
destructive action is taken from the next

action

– Check that the fiber optic cables are

seated properly in the Optical Interface
Board and the SCGT firing card

– Check that the fiber optic cable is not

pinched or damaged

– Complete a resistance check per the

instructions in the manual

– NOTE: SGCTs may not have completely

shorted, and still could read in the kΩ
range – Any devices with low suspect
readings should be changed

– Check the LED status of the SCGT gate

driver card for abnormal readings

– Complete a Gating Test mode check on

the devices

– Verify the associated 20V power supply

is powered and active

– Verify all the power connections to the

SCGT firing card are seated properly

U1B Fbk FO Loss

99

U1C Fbk FO Loss

468

U4A Fbk FO Loss

96

U4B Fbk FO Loss

102

U4C Fbk FO Loss

471

V3A Fbk FO Loss

95

V3B Fbk FO Loss

101

V3C Fbk FO Loss

470

V6A Fbk FO Loss

98

V6B Fbk FO Loss

104

V6C Fbk FO Loss

473

W2A Fbk FO Loss

94

W2B Fbk FO Loss

100

W2C Fbk FO Loss

469

W5A Fbk FO Loss

97

W5B Fbk FO Loss

103

W5C Fbk FO Loss

472

U1A Gat FO Loss

105

INVERTER SGCT FAULT

(Gating Fiber-Optic Loss)

This fault will only occur during the initial

contactor closure and the diagnostic
sequence after a start command. The
inverter monitors the state of the feedback
before a gate pulse is given, and monitors
the feedback after a gate pulse has been
sent. This fault occurs when the feedback

was high from the device before gating, and
is still high from the device after gating. The

drive then assumes the gating pulse must
not have reached the device.

The firmware now completes a diagnostics
sequence immediately after any drive reset,

with the goal of detecting faults before any
destructive action is taken from the next

action

– Check that the fiber optic cables are

seated properly in the Optical Interface
Board and the SCGT firing card

– Check that the fiber optic cable is not

pinched or damaged

– Complete a resistance check per the

instructions in the manual

– NOTE: SGCTs may not have completely

shorted, and still could read in the kΩ

range – Any devices with low suspect
readings should be changed

– Check the LED status of the SCGT gate

driver card for abnormal readings

– Complete a Gating Test mode check on

the devices

– Verify the associated 20V power supply

is powered and active

– Verify all the power connections to the

SCGT firing card are seated properly

U1B Gat FO Loss

111

U1C Gat FO Loss

474

U4A Gat FO Loss

108

U4B Gat FO Loss

114

U4C Gat FO Loss

477

V3A Gat FO Loss

107

V3B Gat FO Loss

113

V3C Gat FO Loss

476

V6A Gat FO Loss

110

V6B Gat FO Loss

116

V6C Gat FO Loss

479

W2A Gat FO Loss

106

W2B Gat FO Loss

112

W2C Gat FO Loss

475

W5A Gat FO Loss

109

W5B Gat FO Loss

115

W5C Gat FO Loss

478