Operator Interface 3-41

7000 “B” Frame

7000-UM150I-EN-P – June 2013

Figure 3.53 – Fault Overview, Enabled

The state of the fault masks which you are currently viewing is
defined to the right of the screen name, i.e. FAULTS OVERVIEW:
DISABLED or FAULTS OVERVIEW: ENABLED. To change the
state of fault masks currently displayed, press the [F7]. Each press of
the [F7] key will toggle the screen to show the masks in the other state.


To change the state of a mask on the FAULTS OVERVIEW screen,
use the [cursor up] and [cursor down] keys to select the desired mask
and press the [enter] key. In the example of Figure 3.52, the “AC
O/V” is currently disabled and is selected. When [enter] is pressed
its mask is enabled, thus removing the fault from this screen as
shown in Figure 3.54. Pressing [F7] toggles the screen to show the
enabled faults, which the AC O/V is one of (Figure 3.55). (If
nothing happens, you do not have proper access to the drive. Exit to
the SETUP screen and refer to the section entitled Enter/Modify an
Access Level
to gain access).

Figure 3.54 – AC O/V Removed From List