Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 457

Advertising
background image

Troubleshooting

7-35

7000 “B” Frame

7000-UM150I-EN-P – June 2013

WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

DC Link Range

126

The value entered for the parameter Link
Inductance (P27) is below a minimum value
for the programmed Drive/Motor ratings.
6P Rectifier – 0.85 pu
18P Rectifier – 0.42 pu
PWM Rectifier – 0.55 pu

– Review DC Link nameplate data
– Review Motor and Drive nameplate data

and verify that all parameters were
entered properly

– Contact factory if the above seems OK

DcLnd Mstr

342

Slave Declined Master-slave only

– Slave has lost communication with hub

PLC, or slave is masked off in parameter

Master Mask

DCBL Battery Low

125

The PowerCap on the DCB-L that powers
the NVRAM where the parameters are
stored is below 2.6 V DC.

– Replace the PowerCap after recording

all the parameters to the terminal,
through Hyperterminal, with a printer or
with DriveTools

– Reinstall the parameters

DCBM Battery Low

188

The PowerCap on the DCB-M is below 2.6
V DC..

– This is not critical unless you ever put

this board in the rectifier position

– Replace the PowerCap

Desync Delay On

48

A transfer from the Line back to Drive
(desync) has been commanded, but it has

been less than 1 minute since the transfer
from Drive to Line (sync) was completed.

As a result, the Output Motor Filter Capacitors
have not had time to adequately discharge.

– Wait for 1 minute and attempt the

desync transfer again.

DPI Power Loss

109

The 12VDC used for SCANport/DPI
communications has dropped below the set
trip level.

– Verify DC/DC power supply output
– Confirm wiring to the CIB from the

DC/DC Power Supply

DPI Ram Overflow

163

DEVELOPMENT ERROR – There is an

internal communication error in the drive
control

– Noise/Grounding Issues
– Confirm grounding is per the RA

drawings

– Contact the Factory

Drive OL

111

A Line Overload warning has been detected,
where the overload condition is calculated
using DC Current Feedback (P322) and

Line Overload Warning (P270) as the point
where the overload warning occurs. (P270)
is programmed as a percentage of the

difference between Line Overload Minimum
(P269)and Line Overload Trip (P163).

– Transient Loading – Check torque limit

and overload settings and Compare
loading to torque settings and trip

settings

Drv in Test Mode

50

The drive Operating Mode (P4) is set to DC
Current Test Mode when an Autotune Test
that turns the motor is initiated

– Place drive back in Normal Mode before

attempting Autotune

Duplcte Mstr

341

Duplicate Master-master only

– The Powerup Config parameter is set to

Master in more than one drive. The first
drive to power up will become the
master