6-66

Component Definition and Maintenance

7000-UM150I-EN-P – June 2013

7000 “B” Frame


+15V - SPGDB TEST

3 phase, 4 wire

XXXVAC

+24V I/O

3phase

TX, XXXV/208V
XXX = 380, 480, 600

DC

FAIL

AC

FAIL

C hold-up

DC/DC

WARN

SPGDB P/S

FAIL

+5V - LOGIC
+/-15V - LOGIC
+/-24V - LEM

+12V - SCANport

+15V - TACH

6

20V

AC/DC

Converter

56 V DC

1500 W

DC/DC

FAIL

Fan

120V, single phase

Fan supply is

XXXV, 3 phase

DC/DC

Converter

Printer

Terminal

relays

20 V

Isolated

Gate Driver

Power Supply

(Optional)

+15V - SPGDB TEST

3 phase, 4 wire

XXXVAC

+24V I/O

3phase

TX, XXXV/208V
XXX = 380, 480, 600

DC

FAIL

AC

FAIL

C hold-up

DC/DC

WARN

SPGDB P/S

FAIL

+5V - LOGIC
+/-15V - LOGIC
+/-24V - LEM

+12V - SCANport

+15V - TACH

6

20V

AC/DC

Converter

56 V DC

1500 W

DC/DC

FAIL

Fan

120V, single phase

Fan supply is

XXXV, 3 phase

DC/DC

Converter

Printer

Terminal

relays

20 V

Isolated

Gate Driver

Power Supply

(Optional)

Figure 6.48 – Standard PowerFlex 7000 “B” Frame control power distribution (without UPS option)


Figure 6.49 illustrates the extended ride-through capabilities of the
control circuit. An UPS must be installed to provide the energy to
supply the AC/DC converter for an extended period of time in case
of a loss of control power. It is assumed that if control power is
interrupted, the medium voltage will also be interrupted and the drive
will not be required to operate the motor until both control and
medium voltage is re-applied.