Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 430

Advertising
background image

7-8

Troubleshooting

7000-UM150I-EN-P – June 2013

7000 “B” Frame

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

DPI Interface

243

This fault typically occurs when you have
the Communication Type (P147) set for
500k (DPI only), and you have a SCANPort

adapter connected to the CIB. SCANPort
operates at 125k, and the DPI can operate
at both speeds. This can also occur if the

SCANPort network attempts to access Port
5, which is internally assigned to DPI.

Note: „MOD A‟ LED on the CIB indicates a

healthy SCANPort Adapter when Green.
„MOD B‟ LED on the CIB indicates a healthy
DPI Adapter when Green.

– Ensure Communication Type is set for

125k for any drive with SCANPort
connections

– Ensure you are not using a SCANPort

splitter with Port 5 active as the drive

internally has assigned Port 5 to DPI,
and this conflict will create a fault

– Cycle power to ensure you

Communication Type change takes
effect

– The final cause could be a CIB Hardware

problem, and the board should be

replaced if the above actions are
unsuccessful

DI Contactor

18

The Drive Input Contactor has opened
without command from the PF7000 drive.

– The drive system needs to have

complete control over all contactors, so
investigation of the specific contactor

fault is required

– Verify contactor feedback
– Verify the control power circuit for the

contactor

– Check permissive string to the contactor

control relay (refer to drawing) -Check

contactor/breaker for physical
malfunction (auxiliaries)

– Check SCB inputs and outputs

DO Contactor

19

The Drive Output Contactor has opened
without command from the PF7000 drive.

OP Contactor

34

The system output contactor has opened
without command from the PF7000 drive.

BP Contactor

20

The Bypass Contactor has opened without
command from the PF7000 drive.

DI Iso Switch

29

The Drive Input Isolation Switch is in the
opposite state than expected, or the state
has changed during operation.

– Depending on the mode of operation

(Normal, System Test, Open-Circuit
Test, DC Current Test, or Open-Loop),
there are specific states for all the
possible system isolation switches (Refer

to the description of the Parameter 192 –
IsolSw/Ctctr Cfg in the parameters

manual)

– Ensure the isolation switches are in the

proper position

– Verify wiring feedback
– Verify isolation switch mechanical

auxiliary setup

DO Iso Switch

30

The Drive Output Isolation Switch is in the

opposite state than expected, or the state
has changed during operation.

OP Iso Switch

32

The System Output Isolation Switch is in the

opposite state than expected, or the state
has changed during operation.

BP Iso Switch

31

The Bypass Isolation Switch is in the
opposite state than expected, or the state
has changed during operation.

Drive OL

191

A Drive Overload condition has been
detected, where the overload condition is

calculated using DC Current Feedback
(P322) and an algorithm based on Drive
Overload Trip (P163) as the absolute trip

level, Drive Overload Delay (P164) as the
base trip delay, and Drive Overload Min

(P269) as initial detection level.

– Transient Loading – Check torque limit

and overload settings and compare

loading to torque settings and trip
settings

– Open Burden Resistor – Check Current

feedback and check the burden resistors

Dvc AK/Snubb

195

Device Anode-Cathode or Snubber fault

– NOT USED IN 5.xxxx

External 1-16

1-16

These are the optional additional External
Faults available when there is an additional
XIO board installed. This is configured with

XIO Ext Faults (P593), and this message

– Review XIO Board Drawing:
– Identify source of Input from External

Fault XIO Board print and investigate the
cause of the fault

Advertising