7-40

Troubleshooting

7000-UM150I-EN-P – June 2013

7000 “B” Frame

WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Line DC Link OV

116

The measured Line DC voltage has
exceeded Line DC Overvoltage Trip (P173),
and instantaneously causes a warning.

– See associated Fault Description

Line Loss

120

The drive has detected a loss of input

voltage from losing the frequency (PLL) lock
on the input voltage. This is designed to be
a faster method of detecting an
undervoltage. The drive responds to this
warning as it does to a Master UV warning.

– Verify the VSB connections and tap

settings, and check resistance of VSB
board – Megger board to confirm

integrity

– Check TSN fusing
– Check actual voltage values on the

Terminal for each bridge and the total

line voltage

– Check for possible source voltage

supply problems

Liq IO Config

(C-Frame Only)

131

The XIO card which was being assigned to
the Liquid Cooling System Faults Input is
not a card which can be used for this
purpose

– Select the proper slot containing the XIO

card which is compatible for Liquid
Cooling System Faults usage.

Liq IO Conflict

(C-Frame Only)

132

The XIO card previously being used for
Liquid Cooling System Faults has been
reassigned for another purpose.

– Check the configuration of all XIO slots

and reassign if necessary.

Logx IO Config

133

The XIO card which was being assigned to

Logix IO (basic PLC functionality) is not a
card which can be used for this purpose

– Select the proper slot containing the XIO

card which is compatible for Logix IO
usage.

Logx IO Conflict

134

The XIO card previously being used for

Logix IO (basic PLC functionality) has been
reassigned for another purpose.

– Check the configuration of all XIO slots

and reassign if necessary.

Master UV

112

The measured value V Master Average
(P136) is less than Line Undervoltage Trip

(P167) with respect to 1/3 Rated Line
Voltage (P18) [for 18-pulse drives], and
Rated Line Voltage (P18) [for 6-pulse and

PWM drives] for the period set by Line
Undervoltage Delay (P168).

– Verify the VSB connections and tap

settings, and check resistance of VSB

board – Megger board to confirm
integrity

– Check TSN fusing
– Check actual voltage values on the

Terminal for each bridge and the total

line voltage

– Check for possible source voltage

supply problems

– Use Multimeter and Oscilloscope to

check voltages on the drive test points

Motor Cap Range

23

The calculated per unit value of the Motor
Filter Capacitor (P128), based on the values

entered for Motor Capacitor kVAR (P20),
Motor Capacitor Volts (P21), and Motor
Capacitor Frequency (P28) is outside of the
normal range of 0.26-0.55 pu.

– Verify capacitor nameplate data and

compare with information entered in
drive

– Contact factory