Specifications – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 26

Advertising
background image

Overview of Drive 1-9

7000 “B” Frame

7000-UM150I-EN-P – June 2013

Description

NEMA

IEC

Power Rating (Air Cooled)

200 to 5,500 hp

150 to 4,100 kW

Motor Type

Induction or Synchronous

Input Voltage Rating

2400V, 3300V, 4160V, 6600V

Input Voltage Tolerance

± 10% of Nominal

Voltage Sag

-30%

Power Loss Ride-Through

5 Cycles (Std)

> 5 Cycles (Optional UPS)

Input Protection

Metal Oxide Varistor (MOV)

Input Frequency

50/60 Hz, +/- 5%

Input Short-circuit Current Withstand

5 Cycle

2400 V – 6600 V 

25 MVA RMS SYM

Basic Impulse Level 

50 kV (0 – 1000m)

Power Bus Design

Copper – Tin plated

Ground Bus

Copper – Tin plated 6 x 51 mm (¼ x 2 in.)

Customer Control Wire Way

Separate and Isolated

Input Power Circuit Protection

Vacuum Contactor with Fused Isolating Switch

or Circuit Breaker

Input Impedance Device

Isolation Transformer or AC Line Reactor

Output Voltage

0 – 2300 V
0 – 3300 V
0 – 4160 V

0 -6000 V, 0 – 6300 V, 0- 6600 V

Inverter Design

PWM

Inverter Switch

Symmetrical Gate Commutated Thyristor (SGCT)

Inverter Switch Failure Mode

Non-rupture, Non-arc

Inverter Switch Failure Rate (FIT)

100 per 1 Billion Hours Operation

Inverter Switch Cooling

Double Sided, Low Thermal Stress

Inverter Switching Frequency

420-540 Hz

Number of Inverter SGCT’s

Voltage

SGCT’s (per phase)

2400 V
3300 V
4160 V
6600 V

2
4
4
6

SGCT PIV Rating
(Peak Inverse Voltage)

Voltage

PIV

2400 V
3300 V
4160 V
6600 V

6500 V
6500 V
6500 V
6500 V

Rectifier Designs

6 Pulse

18 Pulse

Active Front End (PWM)

Rectifier Switch

SCR (6/18 Pulse), SGCT (Active Rectifier)

Rectifier Switch Failure Mode

Non-rupture, Non-arc

Rectifier Switch Failure Rate (FIT)

50 (SCR) 100 (SGCT) per 1 Billion Hours Operation

Rectifier Switch Cooling

Double Sided, Low Thermal Stress

Short-circuit fault rating based on input protection device (contactor or circuit breaker)

BIL derating based on altitudes < 1000 m (3,300 ft.). Refer to factory for derating.

Specifications