Functional Description 5-3

7000 “B” Frame

7000-UM150I-EN-P – June 2013

Speed Command

The function of Speed Command block is to select one of the 13
possible speed command inputs. Parameter Reference Select (2) in
conjunction with Local/Remote selector switch is used to define the
speed command input Speed Command In (276). When the selector
switch is in Local position, the default speed command is the Analog
Speed Potentiometer typically mounted on the LV panel. When the
selector switch is in Remote position, the parameter Reference Select
defines the source of speed command. The options available are:

 3 analog inputs (Speed Pot, Remote 0-10V,

Current Loop: 4-20mA or 0-20mA)

 3 Preset speed commands
 6 DPI/SCANport commands
 1 Preset jog speed command

The above speed commands are used when the drive is in Normal
mode of operation. However PF7000 has many special modes of
operation e.g. test modes or auto-tuning for which different speed
commands are selected. Table 5.A summarizes the speed command
during these special modes.

Table 5.A – Speed Commands for special operating modes of PF7000

Special operating modes of PF7000

Speed Command In(276)

DC test mode

60Hz

Open Circuit

Rated Line Freq(17)

Open Loop

0.1*Rated Line Freq(17)

Rs autotune

2Hz

Ls autotune

Rated Line Freq(17)

Flux Reg autotune

Autotune Spd Cmd(213)

Speed Reg autotune

Autotune Spd Cmd(213)

Demagnetize

Rated Motor Freq(29)

Sync transfer requested

Bypass Freq(159)

The selected Speed Command In is clamped to a minimum and a
maximum level by parameter Spd Cmd Max (290) and Spd Cmd Min
(293) to give Speed Command (277). The maximum value of Speed
Command
cannot be greater than 125% of Base Speed (98).

Note: Contact the factory for applications that require output

frequencies greater than 125% of the motor base speed.