Commissioning 4-61

7000 “B” Frame

7000-UM150I-EN-P – June 2013

Line Terminal Resistance Measurements


Measuring the resistance between the drive line cable terminals will
quickly identify if there is interwiring between the 0

, +20

, and -20

bridges in the isolation transformer.

2U

2V

2W

3W

3V

3U

4W

4V

4U

2U

2V

2W

3W

3V

3U

4W

4V

4U

There are low resistances between phases through a transformer
winding and a high resistance between transformer windings.
Therefore, the expected resistance measurements are listed in the
table below:

Terminal Measurement Points

Expected Resistance

2U  2V  2W

Approximately 0 Ω

3U  3V  3W

Approximately 0 Ω

4U  4V  4W

Approximately 0 Ω

#U  #V  #W

Approximately ∞ Ω




If the measurement results are not as described above, the interwiring
between the isolation transformer and drive needs to be re-inspected.