Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual
Page 220
![background image](/manuals/580783/220/background.png)
Commissioning 4-61
7000 “B” Frame
7000-UM150I-EN-P – June 2013
Line Terminal Resistance Measurements
Measuring the resistance between the drive line cable terminals will
quickly identify if there is interwiring between the 0
, +20
, and -20
bridges in the isolation transformer.
2U
2V
2W
3W
3V
3U
4W
4V
4U
2U
2V
2W
3W
3V
3U
4W
4V
4U
There are low resistances between phases through a transformer
winding and a high resistance between transformer windings.
Therefore, the expected resistance measurements are listed in the
table below:
Terminal Measurement Points
Expected Resistance
2U 2V 2W
Approximately 0 Ω
3U 3V 3W
Approximately 0 Ω
4U 4V 4W
Approximately 0 Ω
#U #V #W
Approximately ∞ Ω
If the measurement results are not as described above, the interwiring
between the isolation transformer and drive needs to be re-inspected.