Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 465

Advertising
background image

Troubleshooting

7-43

7000 “B” Frame

7000-UM150I-EN-P – June 2013

WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Pump Failure

(C-FRAME ONLY)

143

The drive has detected a fault from one of
the pumps in the cooling circuit.

– Verify the Pump O/L settings and

conditions

– Verify the Pump Control Relay status

and auxiliary contact signals.

Queues Cleared

91

This means that the drive had to clear the
fault and warning queues after an upgrade

of the firmware

– This was an issue because the memory

structure changed in 3.xxx firmware

– No action is required

R Stator High

52

Autotune Rs (P219) measured during the
autotune test was higher than 0.20 pu,

indicating the presence of extremely long
motor leads.

– REFER TO THE POWERFLEX 7000

SERIES B MANUAL (CHAPTER 4 –

COMMISSIONING) ON AUTOTUNE
PROCEDURES, RESULTS, AND
ACTIONS

– Ensure motor windings are connected

properly.

Rec Gate Pwr

205

Rectifier Gate driver power supply warning

– The device feedback was not right due

to the power loss in the gate driver
board. This may not only 20VDC PS

problem to SGCT but it can also be on
PS problem on gate driver card.

– This warning can come due to device

failure or device online diagnostic

Rec Heatsink FO

203

While Not Running, the Fiber Optic signal

from the TFB on the Rectifier Heatsink,
connected to Channel A fiber optic receiver
RX7 on FOI-L-A is not present. This is only

a fault while not running. If this occurs while
running it will appear as a warning.

– Check TFB and FOI board for power
– Check the Fiber Optic cables are

properly seated in the transmitters and

receivers

– Check the fiber optic cable for kinks,

bends, breaks that could be blocking the
signal

– This can occur if the sensor is not

connected to the TFB

– NOTE: This is a warning because the

drive should not fault on the loss of the
signal while running. There is no
imminent danger to the drive, but the
user needs to be aware that there is a
temperature feedback signal missing.

Rec ChannelB FO

204

Not Normally Used: While Not Running, the

Fiber Optic signal from the optional TFB
connected to Channel B fiber optic receiver

RX7 on FOI-L-B is not present. This is only
a fault while not running. If this occurs while
running it will appear as a warning.

Rec Heatsink OT

121

The temperature detection on the Rectifier
Heatsink, connected to Channel A fiber optic

receiver RX7 on FOI-L-A, has exceeded
Rectifier Heatsink Temperature Warning
(P112).

– Confirm actual temperature in

parameters is not higher than the

warning value – If so, investigate the
conditions of the drive (ambient / loading
/ elevation / ventilation/ filter status /

heatsink clogging)

– Check TFB and FOI board for power

and fiber optic integrity

– Check the sensor and temperature

offline (ambient) for accuracy

Rec ChannelB OT

122

Not Normally Used – The temperature
detection on a Rectifier Heatsink, connected

to fiber optic receiver RX7 on FOI-L-B, has
exceeded Rectifier Temperature Warning
Channel B (P526).