7-12

Troubleshooting

7000-UM150I-EN-P – June 2013

7000 “B” Frame

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Line Fltr Cap OV

176

The measured line voltage Vline Bridge
(P696) has exceeded Line Overvoltage Trip
(P165) for the duration set in Line

Overvoltage Delay (P166). This is the only
uncompensated voltage, representing the
voltage on the input to the bridge. All other

voltages in the line-side are compensated
using L commutation.

– Verify the parameters are set properly
– Verify VSB connections and tap settings,

resistor values, and grounds

– This is less likely to be caused by a true

Line Overvoltage and more likely to be

due to the effects of capacitive leading
VARs on a high-impedance system

– Tap down the input if possible

Line Harmonic OV

200

The drive has detected a steady-state
resonance-induced overvoltage on the line.

This is defined at the level set in Harmonic
OV Trip (P675) for the delay Harmonic OV
Delay (P676) (on top of normal line voltage)

for 1 second. The drive only detects the 5

th

harmonic to eliminate nuisance faults from
capacitor charging events.

– Verify waveforms show excessive

harmonics using oscilloscope on SCBL

unfiltered voltage testpoints

– Investigate sources for excessive

harmonics on customer power system

– Contact factory for possible re-tuning of

input filter

Line HCS Power

175

The power supplied to the DC Link Hall-
Effect Current Sensor (±24VDC) is
monitored on the control board and will fault
the drive if the voltage is out of tolerance.

– Verify the DC voltage on the DC/DC

supply, at the SCB-L terminals, and at
the Current Sensor

– Check the Current Sensor wiring and

ensure all connections are per the

Electrical Drawing

Line Heartbeat

25

The DCB-M has detected the loss of the
heartbeat signal from the DCB-L

– Verify DC Control voltages to both DCBs
– Possible Failed DCB – Check LED status

of both boards and compare with table in
the manual – Recycle power and replace
board if necessary

Line Neutral OV

192

For SCR rectifiers, the Neutral-to-Ground
voltage calculated from the measured line

voltages has exceeded Ground Fault
Overvoltage Trip (P587) for the duration set

in Ground Fault Overvoltage Delay (P588).
For PWM rectifier, the Neutral-to-Ground
voltage is measured directly from the Line

Filter Capacitor Neutral. In both cases, the
actual value is displayed in V Neutral Line
(P589)

– DESIGNED FOR PWM-Rectifier ONLY:
– Insulation Failure – Megger the motor

insulation/motor cables/drive insulation to

ground

– Verify the integrity of the input grounding

network if applicable

– Megger the input Isolation Transformer

Secondary/Input Cables to ground

– Verify Parameter settings are appropriate

for AC Line Reactor or Isolation
Transformer drives

– Verify the integrity of Line Filter

Capacitors (for PWM rectifier drives),
looking for short circuits or signs of
physical damage. Refer to Chapter 6 of
the User‟s Manual for detailed
instructions on Testing Filter Capacitors.