6-34

Component Definition and Maintenance

7000-UM150I-EN-P – June 2013

7000 “B” Frame

Heatsink Replacement

There are 2 different styles of heatsinks used in the PowerFlex drive
depending on current ratings and thermal requirements. The lighter
aluminum heatsink has a very fine ventilation pattern through the
heatsink. The heavier copper heatsink has a basic ventilation pattern
with larger openings for airflow, and will often have a grill mounted
on the front of the heatsink to help restrict the flow.

Aluminum Heatsink

Copper Heatsink


The copper heatsinks can weigh about 9kg (20 lbs.), while the
aluminum heatsinks will only weigh approximately 4kg (9 lbs.)


1. Ensure there is no power to the equipment.

A T T E N T I O N

A T T E N T I O N

To prevent electrical shock, ensure the main
power has been disconnected before working on
the drive. Verify that all circuits are voltage free
using a hot stick or appropriate voltage-
measuring device. Failure to do so may result in
injury or death.