Component Definition and Maintenance 6-67

7000 “B” Frame

7000-UM150I-EN-P – June 2013


120V, single phase

AC

FAIL

6

20V

UPS

2kVA

UPS

on

bypass

batt low

on

batt

AC

FAIL

DC

FAIL

Fan

Printer

Terminal

Relays/contactor

DC/DC

CONVERTER

C hold-up

+24V - I/O

+5V - LOGIC
+/-15V - LOGIC
+/-24V - LEM

+12V - SCANPORT

+15V - TACH

+15V - SPGDB TEST

Fan supply

is XXXV,

3 phase

3 phase

transformer

XXXV/208V

3 phase,4 wire

XXXVAC

AC/DC

CONVERTER

56 VDC

@

300W

AC/DC

CONVERTER

56V DC

@

1500W

20 V

ISOLATED

GATE DRIVER

POWER SUPPLY

DC/DC

FAIL

DC/DC

WARN

SPGDB P/S

FAIL

DC

FAIL

(Optional)

120V, single phase

AC

FAIL

6

20V

UPS

2kVA

UPS

on

bypass

batt low

on

batt

AC

FAIL

DC

FAIL

Fan

Printer

Terminal

Relays/contactor

DC/DC

CONVERTER

C hold-up

+24V - I/O

+5V - LOGIC
+/-15V - LOGIC
+/-24V - LEM

+12V - SCANPORT

+15V - TACH

+15V - SPGDB TEST

Fan supply

is XXXV,

3 phase

3 phase

transformer

XXXV/208V

3 phase,4 wire

XXXVAC

AC/DC

CONVERTER

56 VDC

@

300W

AC/DC

CONVERTER

56V DC

@

1500W

20 V

ISOLATED

GATE DRIVER

POWER SUPPLY

DC/DC

FAIL

DC/DC

WARN

SPGDB P/S

FAIL

DC

FAIL

(Optional)


Figure 6.49 – Standard PowerFlex 7000 “B” Frame control power distribution (with UPS option)




To reduce the size of UPS needed, the loads on the AC/DC converters
are separated into two distinct loads: the IGDPS boards and the
DC/DC power supply.


The IGDPS load is only needed when the drive is in the normal
operating mode and running the motor. During interruption of
control and medium voltage, the IGDPS load demand on the AC/DC
will be not be required. Only the DC/DC will remain energized for
an extended period of time after loss of control power. The DC/DC
converter will power the main control boards and keeps them fully
functional.