Cable Insulation

The cable insulation requirements for the PowerFlex 7000 drive are
given in the tables below.

A T T E N T I O N

A T T E N T I O N

Voltage ratings shown in the following
tables are peak line to ground. Some cable
manufacturers rate voltage line to line RMS.
Ensure the cable meets the rating specified
in the following tables.


Cable Insulation Requirements for 6P / PWM Drives with Line Reactor

System Voltage (V, RMS)

Cable Insulation Rating (kV)

(Maximum Peak Line to Ground)

Line Side

Machine Side

2400

2.2



4.1

3000



2.75



5.12

3300



3.0



5.63

4160



3.8

7.1

6000



5.5

10.8

6300



5.8

11.4

6600



6.0

11.8


Cable Insulation Requirements for 18P and 6P / PWM Drives with Isolation

Transformer

System Voltage (V, RMS)

Cable Insulation Rating (kV)

(Maximum Peak Line to Ground)

Line Side

Machine Side

2400



4.1



2.2

3000



5.12



2.75

3300



5.63



3.0

4160

7.1



3.8

6000

10.8



5.5

6300

11.4



5.8

6600

11.8



6.0


Cable Insulation Requirements for “Direct-to-Drive” Technology

System Voltage (V, RMS)

Cable Insulation Rating (kV)

(Maximum Peak Line to Ground)

Line Side

Machine Side

2400



2.2



2.2

3000



2.75



2.75

3300



3.0



3.0

4160

3.8



3.8

6000

5.5



5.5

6300

5.8



5.8

6600

6.0



6.0