Commissioning 4-49

7000 “B” Frame

7000-UM150I-EN-P – June 2013

Now press SETUP [F8] to get to
Parameters, and then Enter. You
should be on Feature Select, the first
group.


Press Enter, and then use the down
arrow to get to Operating Mode.


Press Enter and use the down arrow to
get to Gating Test. Press Enter, and
you will now be in gating test mode.


A T T E N T I O N

A T T E N T I O N

Ensure that the drive is no longer running in
test mode prior to applying medium voltage to
the drive line-up. Failure to do so may result in
equipment damage.