Troubleshooting

7-39

7000 “B” Frame

7000-UM150I-EN-P – June 2013

WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Iso Fn2 Cntr

330

Isolation Transformer Fan 2 contactor

– Isolation transformer Fan 2 status is

NOT HIGH while the drive asked the
contactor to be closed

Iso Fn1 Loss

331

Isolation Transformer Fan 1 Loss

– Drive looks for Fan 1 status or air

pressure. If any of this lost the drive give
this warning.

Iso Fn2 Loss

332

Isolation Transformer Fan 2 Loss

– Drive looks for Fan 2 status or air

pressure. If any of this lost the drive give

this warning.

IsoTx Air Filter

(A-Frame Only)

26

The Pressure sensed by the pressure
transducer in the integral Isolation
Transformer section (as a voltage) has
dropped below the value set in Pressure
Value Transformer Warning (P655).

– Verify fan rotation
– Blocked airflow in the filters / ducting (if

installed) – Clean as required

– Improper Warning settings – Verify

Pressure Value voltage level when

running with clear air flow

– Verify Alarm and Trip set-up procedure

was completed adequately and adjust as
necessary

– Verify for drives with external ducting that

there is sufficient air to the drive input

– Verify supply voltage to pressure

transducer, and confirm output is stable

IxoTx Fan On

328

Isolation Transformer Fan ON warning

– Isolation transformer Fan status is high

while it should be low.

L Comm Low

55

Indicates that the Autotune Lc (P217)
measured was less than 0.02 pu and the L
Commutation (P140) will have to be tuned
manually.

– REFER TO THE POWERFLEX 7000

SERIES B MANUAL (CHAPTER 4 –
COMMISSIONING) ON AUTOTUNE
PROCEDURES, RESULTS, AND
ACTIONS

L Comm High

56

Indicates that the Autotune Lc (P217)
measured was greater than 0.15 pu and the
L Commutation (P140) will have to be tuned
manually.

L Leakage Low

59

Indicates that the Autotune Ls (P220)
measured was less than 0.15 pu.

– REFER TO THE POWERFLEX 7000

SERIES B MANUAL (CHAPTER 4 –

COMMISSIONING) ON AUTOTUNE
PROCEDURES, RESULTS, AND

ACTIONS

L Leakage High

60

Indicates that the Autotune Ls (P220)
measured was greater than 0.30 pu.

L Magnetize Low

61

Indicates that the Autotune L mag (P221)
measured was less than 2.00 pu, and L

magnetizing (P131) will have to be tuned
manually.

L Magnetize High

62

Indicates that the Autotune L mag (P221)
measured was greater than 10.00 pu, and L
magnetizing (P131) will have to be tuned

manually.

Line Cap Range

124

In PWM rectifier drives, the calculated per
unit value of the Line Filter Capacitor

(P133), based on the values entered for
Line Capacitor kVAR (P15), Line Capacitor
Volts (P16), and Line Capacitor Frequency
(P32) is outside of the normal range of 0.35-
0.55pu.

– Verify capacitor nameplate data and

compare with information entered in
drive