Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 28

Advertising
background image

Overview of Drive 1-11

7000 “B” Frame

7000-UM150I-EN-P – June 2013

Description

NEMA

IEC

Control Power

208-575 V, 3 Phase, 50/60 Hz

External I/O

16 Digital Inputs, 16 Digital Outputs

External Input Ratings

50-60 Hz AC or DC

120-240 V – 1 mA

External Output Ratings

50-60 Hz AC or DC

30-260 V – 1 Amp

Analog Inputs

(1) Isolated, (1) Non-isolated, 4-20 mA or 0-10 V (250 ohm)

Analog Resolution

• Analog input 12 Bit (4-20 mA)

• Internal parameter 32 Bit resolution

• Serial Communication 16 Bit resolution (.1Hz)

(Digital Speed Reference)

Analog Outputs

(1) Isolated, (7) Non-isolated,
4-20 mA or 0-10 V (600 ohm)

Communication Interface

SCANPort /DPI

Scan Time

Internal ScanPort – 10 ms

Internal DPI – 5 ms

Communications Protocols
(Optional)

RS232/422/485

Ethernet

DH485

Interbus

Remote I/O

LON Works

DeviceNet

Can Open

ControlNet

Profibus

Modbus/Modbus Plus

Johnson Controls

Enclosure

NEMA 1

IP21

Lifting Device

Standard / Removable

Mounting Arrangement

Mounting Sill channels

Structure Finish

Epoxy Power – Paint

Exterior Sandtex Light Grey (RAL 7038) – Black (RAL 8022)

Internal – Control Sub Plates – High Gloss White (RAL 9003)

Interlocking

Key provision for customer input Disconnecting Device

Corrosion Protection

Unpainted Parts (Zinc Plated / Bronze Chromate)

Ambient Temperature

0° to 40°C (32°F to 104°F)

Fiber Optic Interface

Rectifier – Inverter – Cabinet (Warning / Trip)

Door Filter

Painted Diffuser with Matted Filter Media

Door Filter Blockage

Air Flow Restriction (Trip / Warning)

Storage and Transportation
Temperature Range

-40°C to 70°C (-40°F to 185°F)

Relative Humidity

Max. 95% Non-Condensing

Altitude (Standard)

0 to 1000 m (0 to 3300 ft.)

Altitude (Optional)

1001 to 5000 m (0 to 16400 ft.)

Seismic (UBC Rating)

1, 2, 3, 4