Specifications (cont.) – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 27

Advertising
background image

1-10

Overview of Drive

7000-UM150I-EN-P – June 2013

7000 “B” Frame


Description

NEMA

IEC

Number of Rectifier Devices
per phase

Voltage

6-Pulse

18-Pulse

AFE

2400 V
3300 V
4160 V
6600 V

2
4
4
6

6
6
6
6

2
4
4
6

SCR PIV Rating
(Peak Inverse Voltage)

Voltage

6-Pulse

18-Pulse

AFE

2400 V
3300 V
4160 V
6600 V

6500 V
6500 V
6500 V
6500 V

4500 V
4500 V
4500 V
6500 V

6500 V
6500 V
6500 V
6500 V

Output Current THD (1

st

– 49

th

)

< 5%

Output Waveform to Motor

Sinusoidal Current / Voltage

Medium Voltage Isolation

Fiber Optic

Modulation techniques

SHE (Selective Harmonic Elimination)

PWM (Pulse Width Modulation)

Control Method

Digital Sensorless Direct Vector

Full Vector Control with Tach Feedback (Optional)

Tuning Method

Auto Tuning via Setup Wizard

Speed Regulator Bandwidth

5-25 Radians / Second

Torque Regulator Bandwidth

15-50 Radians / Second

Speed Regulation

0.1% without Tachometer Feedback

0.01-0.02% with Tachometer Feedback

Acceleration/Deceleration Range

Independent Accel/Decel – 4 x 30 sec.

Acceleration/Deceleration Ramp
Rates

4 x Independent Accel/Decel

S Ramp Rate

Independent Accel/Decel – 2 x 999 sec.

Critical Speed Avoidance

3 x Independent with Adjustable bandwidth

Stall Protection

Delay / Speed

Load Loss Detection

Adjustable level, delay, speed set points

Control Mode

Speed or Torque

Current Limit

Adjustable in Motoring and Regenerative

Output Frequency Range

0.2-75 Hz

Service Duty Rating

Normal Duty

Heavy Duty

110% Overload for 1

minute every 10

minutes (Variable

Torque Load)

150% Overload for 1 minute

every 10 minutes

(Constant Torque Load)

Typical VFD Efficiency

> 98% (6/18 Pulse)

> 97.5% (AFE)

Contact Factory for Guaranteed Efficiency

of Specific Drive Rating

VFD Noise Level

< 85 dB(A) per OSHA Standard 3074

Regenerative Braking Capability

Inherent – No Additional Hardware or Software Required

Flying Start Capability

Yes – Able to Start into and Control a Spinning Load in

Forward or Reverse Direction

Operator Interface

40-character, 16-line formatted text

0.1 Hz Display speed resolution

Languages

English

Spanish

French

Chinese

Based on a motor 50 or 60 Hz base frequency

Redundant fan and fan exhaust ducting options will affect noise level

Specifications (cont.)

Advertising