7-32

Troubleshooting

7000-UM150I-EN-P – June 2013

7000 “B” Frame

WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Bypass UV

185

The measured Line-Side Bypass Voltage is
less than Line Undervoltage Trip (P167) for
the period set by Line Undervoltage Delay

(P166).

– Verify the VSB connections and tap

settings, and check resistance of VSB
board – Megger board to confirm integrity

– Check for possible source voltage

supply problems

– Use Multimeter and Oscilloscope to

check voltages on the drive test points

Bypass Volt UB

186

The measured Line-Side Bypass Voltage
has exceeded the value set in Line Voltage

Unbalance Trip (P271) for the duration set in
Line Voltage Unbalance Delay (P272).

– Verify the VSB connections and tap

settings, and check resistance of VSB

board – Megger board to confirm integrity

– Check for possible source voltage

supply problems

– Use Multimeter and Oscilloscope to

check voltages on the drive voltage test

points

CIB Battery Low

159

The battery on the CIB that powers the
NVRAM has reached a preset low level of
2.6VDC.

– Replace the PowerCap on the CIB

board

Conductivity Hi

(C-FRAME ONLY)

147

The measured conductivity is greater than
1 μS/cm

3

.

– Verify that no foreign debris has entered

the system (iron piping, non-deionized
water, etc.)

– There is no immediate need for action,

but be prepared to change the de-ionizing
cartridge and run the system, verifying

that the conductivity is decreasing

Coolant Level Lo

(C-FRAME ONLY)

148

The level of the coolant in the reservoir has
dropped below the low level warning

indicator, activating the warning.

– You will lose coolant over time through

evaporation, but you should still verify

that there are no slow leaks in the
system

– Add de-ionized water to the system

since this is what normally evaporates,
and check the coolant mixture with a
glycol tester

Coolant Temp Low

(C-FRAME ONLY)

145

The measured coolant temperature has
dropped below 10°C (50°F). The warning

will not clear until the temperature rises
above 15°C (58°F).

– Verify that the thermostatic bypass valve

(V10) was not left open

– Warm up the control room ambient to

get the drive to an operational level

Coolant Temp Hi

(C-FRAME ONLY)

146

The measured coolant temperature has
exceeded 48°C (120°F). The warning can
not be cleared until the temperature has
dropped below 44°C (110°F).

– Verify the heat exchanger fans are

operating

– Verify that the thermostatic valve is fully

opened

– Check that all valves are in the normal

operating position

Ctrl Power Loss

191

This warning tells the drive that the control
power has dipped, and this is used in the

Autorestart feature algorithm as an indicator
to tell the drive to stop gating and wait for

control power to return

– Investigate reliability of the control power
– Ensure the drive operates as expected

when there is a control power outage

(UPS must be installed)

Advertising