Troubleshooting

7-47

7000 “B” Frame

7000-UM150I-EN-P – June 2013

WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

XIO Card #1-6 Loss

81-86

An XIO card has dropped off the
communications link between the XIO cards
and the CIB.

– Reset the board in an attempt to re-

establish communications.

– Check all connections between the

Customer Interface Board and the

jumpers between individual adapters

– Verify the status of all XIO adapters by

comparing the LED status to the table in

the manual.

XIO Power Loss

108

The 24V to the XIO boards has dropped

below the set trip level, which is 95% of
rated voltage.

– Verify DC/DC power supply output
– Confirm wiring to the CIB from the

DC/DC Power Supply

– Check XIO LED status and compare to

values in the manual

Zero Slip

28

The value for Rated Motor RPM (P26) is the

same as speed calculated from Motor Poles
(P99) and Rated Motor Frequency (P29).

– Verify Rated Motor RPM is less than

synchronous speed

U1A Device Wrn

228

INVERTER SGCT WARNING

FOR REDUNDANT DEVICES or N-1
CAPABILITY ONLY

This warning will only occur during the initial

contactor closure and the diagnostic
sequence after a start command. The
inverter monitors the state of the feedback

before a gate pulse is given, and monitors
the feedback after a gate pulse has been

sent. The SGCT has smart diagnostics, so
the feedback may indicate short before
firing, and if the pulse is received and the

device is really shorted, the diagnostic will
toggle the feedback to let you know the

problem is with the device, or the power
supply for that device.

The firmware now completes a diagnostics
sequence immediately after any drive reset,
with the goal of detecting problems before
any destructive action is taken from the next
action

– Complete a resistance check per the

instructions in the manual

– NOTE: SGCTs may not have completely

shorted, and still could read in the kΩ
range – Any devices with low suspect

readings should be changed in matched
sets during the next outage

– Check the LED status of the SCGT gate

driver card for abnormal readings

– Complete a Gating Test mode check on

the devices

– Verify the associated 20V power supply

is powered and active

– Verify all the power connections to the

SCGT firing card are seated properly

– NOTE: For Redundant devices, there

will be no change in the drive operation.
For N-1 drives, the drive will attempt to
run at a load/speed combination that
does not exceed the voltage rating of the
remaining devices.

U1B Device Wrn

234

U1C Device Wrn

246

U4A Device Wrn

231

U4B Device Wrn

237

U4C Device Wrn

249

V3A Device Wrn

230

V3B Device Wrn

236

V3C Device Wrn

242

V6A Device Wrn

233

V6B Device Wrn

239

V6C Device Wrn

251

W2A Device Wrn

229

W2B Device Wrn

235

W2C Device Wrn

247

W5A Device Wrn

232

W5B Device Wrn

238

W5C Device Wrn

250