Tool / Parts / Information Requirements


The following is a list of the tools recommended for proper
maintenance of the PF7000 drives. Not all of the tools may be
required for a specific drive preventive procedure, but if we were to
complete all of the tasks listed above the following tools would be
required.


Tools

 100 MHz Oscilloscope with minimum 2 Channels and memory
 5kV DC Megger
 Digital Multimeter
 Torque Wrench
 Laptop Computer with Relevant Software and Cables
 Assorted Hand Tools (Screwdrivers, Open Ended Metric

Wrenches, Metric Sockets, etc.)

 5/16 Allen Keys
 Speed Wrench
 Feeler Gauge
 Vacuum Bottle Checker or AC-Hipot
 Minimum of 7.5 kV Hotstick / Potential Indicator
 Minimum of 10 kV Safety Gloves
 Vacuum Cleaner with Anti-static Hose
 Anti-static Cleaning Cloth

No. 30 Torx Driver

Documentation

 PF7000 User Manual – Publication 7000-UM150_-EN-P
 PF7000 Parameters Manual – Publication 7000-TD001_-EN-P
 MV 400A Vacuum Contactor, Series D User Manual

– Publication 1502-UM050_-EN-P

 MV 400A Vacuum Contactor, Series E User Manual

– Publication 1502-UM052_-EN-P

 Drive-Specific Electrical and Mechanical Prints
 Drive-Specific Spare Parts List


Materials

 Torque Sealer (Yellow) Part number --- RU6048
 Electrical Joint Compound ALCOA EJC no. 2 or approved

equivalent (for Power Devices)

 Aeroshell no. 7 Part number 40025-198-01 (for Vacuum

Contactors)