Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 443

Advertising
background image

Troubleshooting

7-21

7000 “B” Frame

7000-UM150I-EN-P – June 2013

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Slave1 CurrentUB

164

The measured and calculated phase
currents in the Slave 1 Bridge have
exceeded the value set in Line Current

Unbalance Trip (P108) for the duration set in
Line Current Unbalance Delay (P109).

– Verify that all Current Transformer

connections are connected properly and
that no wires are reversed – Ring-out

wires to verify connections

– Check grounding on CTs
– Ensure that all plugs are firmly

connected in the SCBL

– Check that all input voltages are

balanced

– Verify Parameter settings
– Check the burden resistors
– Verify the Input Capacitor values if

installed

– Verify that there are no open sharing

resistors

– Verify all Line Thyristors are firing in

Gating Test Mode

Slave2 CurrentUB

165

The measured and calculated phase
currents in the Slave2 Bridge have

exceeded the value set in Line Current
Unbalance Trip (P108) for the duration set in
Line Current Unbalance Delay (P109).

Slave1 Phasing

168

The voltage phasing on the Slave1 bridge is
not phased the same as the voltages on the

Master bridge.

– Verify cables are terminated correctly
– Verify the feedback wires from the

terminals to the VSB is terminated correctly

– The faults can be masked, and then the

voltages and phasing can be checked
using the test points on the SCB-L, being
aware that there will be phase

differences between the master and
secondary bridges depending on the

drive configuration. Refer to Manual.

Slave2 Phasing

169

The voltage phasing on the Slave 2 bridge is
not phased the same as the voltages in the

Master Bridge.

Slave1 VoltageUB

161

The measured phase voltages in the Slave

1 Bridge have exceeded the value set in
Line Voltage Unbalance Trip (P271) for the
duration set in Line Voltage Unbalance

Delay (P272).

– CHECK TSN FUSING
– Verify the VSB connections and tap

settings, and check resistance of VSB
board – Megger board to confirm
integrity

– Check actual voltage values on the

Operator Interface terminal for each
bridge and the total line voltage

– Check for possible source voltage supply

problems

– Use Multimeter and Oscilloscope to

check voltages on the drive voltage test
points

Slave2 VoltageUB

162

The measured phase voltages in the Slave2

Bridge have exceeded the value set in Line
Voltage Unbalance Trip (P271) for the
duration set in Line Voltage Unbalance

Delay (P272).

Spd Cmd Loss

317

The drive has lost communication with the

device responsible for providing the speed
command to the drive. This has been set to
annunciate as a fault. The drive will

configure the Speed Command Loss as a
fault when the associated bit in Adapter
Loss Mask (P175) is set to a 1. Setting the
bit to 0 will cause the drive to indicate a
warning and run at the last commanded
speed.

– Ensure that the SCANport device is

powered

– Verify the SCANport light status and

ensure the device is operating properly

– Verify the customer SCANport network is

properly communicated with the device

– Check CIB LED status
– Cycle control power to the drive
– Change the Adapter and/or CIB if all

attempts to restore communication fail

Advertising