GV3000/SE AC Drive Software Reference, Version 6.06

4.6.2 Second Menu General Parameter Descriptions (P.007 to P.099)

An unasserted (open) or asserted (closed) input will select the input functions as

shown in table 4.2. If a function is not configured, the unasserted (open) state will be

applied.

P.007 Terminal Strip Digital Inputs Configure

The GV3000/SE

drive provides

multiple

configurations of

digital inputs 6, 7,

and 8 on the terminal

strip. This parameter

determines how

these inputs are

used.

The P.008 (Terminal

Strip Speed

Reference Source)

selection will limit the

selection of P.007

because the P.008

selection may use

one or more of digital

inputs 6 through 8.

Parameter Range:

Preset Configurations of Inputs 6, 7, and 8

Digital Input 6 Digital Input 7 Digital Input 8

(Terminal 19) (Terminal 18) (Terminal 17)

0 = FWD/REV RAMP 1/2

REM/LOC

1 =

Not used FWD/REV

RAMP 1/2

2 =

Not used

FWD/REV REM/LOC

3 =

Not used RAMP 1/2 REM/LOC

4 =

Not used

Not used

FWD/REV

5 =

Not used

Not used

RAMP 1/2

6 =

Not used

Not used

REM/LOC

7 =

Not used

Not used

Not used

8

*

= FWD/REV TRQ/SPD REM/LOC

9* = Not used TRQ/SPD REM/LOC

10* = Not used

TRQ/SPD

FWD/REV

11* = Not used TRQ/SPD

RAMP 1/2

12* = Not used Not used

TRQ/SPD

*

Vector regulation only.

Default Setting:

0

Parameter Type:

Configurable

Refer also to parameters:

P.008 Terminal Strip Speed Reference Source

!

ATTENTION: If a maintained start contact is used when the control

source = rE, switching from local to remote from the terminal strip will

cause power to be applied to the motor if the remote start contact is

closed. Stay clear of rotating machinery in this case. Failure to observe

this precaution could result in bodily injury.

Table 4.2 – Function Selection for Digital Inputs 6, 7, and 8

Input

Open (Unasserted)

Closed (Asserted)

FWD/REV

Forward

Reverse

RAMP 1/2

Ramp 1

Ramp 2

REM/LOC

Remote

Local

TRQ/SPD

Torque

Speed

Advertising