U.040 outer control loop feedback source, U.041 outer control loop lead/lag select – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 172

Advertising
background image

4-86

GV3000/SE AC Drive Software Reference, Version 6.06

The feedback signal is fed through a lead/lag block which can be configured as a

lead/lag, lag/lead, or null (bypassed) function using parameter U.041 (Outer Control

Loop Lead/Lag Select). See Appendix H for the outer control loop block diagram.

See Appendix H for the outer control loop block diagram.

U.040 Outer Control Loop Feedback Source

This parameter

specifies what is

used as the outer

loop feedback signal.

Parameter Range:

0 = Terminal strip analog input scaled

(see Appendix G)

1 = Speed loop PI output (torque reference,

4095 = 150% torque)

Default Setting:

0

Parameter Type:

Configurable

Refer also to parameters:

U.041 Outer Control Loop Lead/Lag Select

U.042 Outer Control Loop Lead/Lag Low Frequency

U.043 Outer Control Loop Lead/Lag Ratio

U.044 Outer Control Loop Reference Gain

U.045 Outer Control Loop Proportional Gain

U.046 Outer Control Loop Integral Gain

U.047 Outer Control Loop Trim Range Percentage

U.048 Outer Control Loop Proportional Trim Enable

U.041 Outer Control Loop Lead/Lag Select

This parameter

selects whether the

outer control loop

feedback lead/lag

block will operate as

a lead/lag, a

lag/lead, or a null

function (bypassed).

Parameter Range:

0 = Bypass
1 = Lead/lag
2 = Lag/lead

Default Setting:

0

Parameter Type:

Tunable

Refer also to parameters:

U.040 Outer Control Loop Feedback Source

U.042 Outer Control Loop Lead/Lag Low Frequency

U.043 Outer Control Loop Lead/Lag Ratio

U.044 Outer Control Loop Reference Gain

U.045 Outer Control Loop Proportional Gain

U.046 Outer Control Loop Integral Gain

U.047 Outer Control Loop Trim Range Percentage

U.048 Outer Control Loop Proportional Trim Enable