Programming Reference

4-65

H.018 Volts/Hertz Curve Type

(continued)

Figure 4.13 – Volts/Hertz Curve Selection

H.019 Identification Result

This parameter

displays the result of

the identification

procedure. Normally,

the identification

procedure will be

successful, and the

value in H.019 will

be = 0.

Parameter Range:

0 = Identification procedure successful. No fault.
1 = A logged error aborted the identification

procedure. Refer to section 5.3 for how to

determine the cause of the fault. Remove the

cause and repeat the procedure.

2 = A function loss aborted the identification

procedure. Depending on Function Loss

Response (P.026), this is or is not logged.

Remove the cause and repeat the procedure.

3 = A stop command aborted the identification

procedure. Repeat the procedure without

stopping.

4 = The identification procedure aborted because

the measured current feedback signal is too low.

Feedback signal elements or wiring is defective.

Check motor connections, inverter wiring, and

feedback devices (current sensors). Repeat

procedure.

6 = Calculation result based on identification

procedure measurements is out of range. Check

causes of incorrect measurements, such as

motor connections. Repeat procedure.

Default Setting:

0

Parameter Type:

Read only

Refer also to parameters:

H.020 Identification Request

Motor

Voltage
(H.000)

Volts

Hz

Motor

Base Frequency

(H.001)

Motor

Voltage
(H.000)

Volts

Hz

Motor

Base Frequency

(H.001)

Motor

Voltage
(H.000)

Volts

Hz

Motor

Base Frequency

(H.001)

Linear (0)

Optimized (1)

Squared (2)