P.005 current limit, P.006 second menu password – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 96

Advertising
background image

4-10

GV3000/SE AC Drive Software Reference, Version 6.06

For V/Hz regulation: Current limit is set as a percentage of the Power Module rated

amps with a maximum value of 110%. 110% current limit equals the current value in

parameter P.095 (Power Module Output Amps).

When the output current attempts to exceed the preset current limit, the output voltage

and frequency will be lowered as the GV3000/SE drive reduces output current.

For vector regulation: Current limit is a percentage of the value entered in U.004.

The output current will be limited to the current limit value, which may result in motor

speed decreasing or the acceleration/deceleration time being extended.

Note that if the password is entered to enable access to the Second Menu

parameters, the password must then be re-entered to disable access.

P.005 Current Limit

This parameter

provides the means

to limit motor stator

current while running

at constant speed or

during acceleration.

Parameter Range:

50 to 110% (V/Hz)

*

U.006 to 150% (vector)

Default Setting:

100% (V/Hz)

150% (vector)

Parameter Type:

Tunable

Refer also to parameters:

P.095 Power Module Output Amps

H.002 Motor Nameplate Amps

U.004 Motor Nameplate Amps

U.006 Magnetizing Current Percent

*

For M/N 125R4140, the maximum Current Limit setting is 100% when P.047 = 8 kHz carrier frequency.

P.006 Second Menu Password

This parameter is

used to

enable/disable

access to Second

Menu General (P),

Vector (U),

Volts/Hertz (H), and

RMI (r) parameters.

Refer to section 4.6.1

of this manual for

more information

about this password.

Parameter Range:

0 to 9999; 107 = password

Default Setting:

N/A

Parameter Type:

Tunable

Refer also to parameters:

N/A

!

ATTENTION: It is the user’s responsibility to determine how to distribute

the second menu password. Reliance Electric is not responsible for

unauthorized access violations within the user’s organization. Failure to

observe this precaution could result in bodily injury.