P.052 auto/man key disable – Rockwell Automation GV3000/SE AC Gen. Purpose and Vector Drive Software Start-Up and Ref. Manual User Manual

Page 128

Advertising
background image

4-42

GV3000/SE AC Drive Software Reference, Version 6.06

When this parameter is set to ON, the AUTO/MAN key is functional only from the
selected control source. This parameter can be used to protect against inadvertent
reference change when the drive is controlled from the terminal strip (P.000 = rE) or
the option port (P.000 = OP).

Table 4.6 details whether the AUTO/MAN key is active based on the selected control
source and P.052.

Note that if P.000 = rE, but the REMOTE/LOCAL switch at terminal 17 is set for
LOCAL (closed), the AUTO/MAN key is active even if P.052 is set to ON.

P.052 AUTO/MAN Key Disable

This parameter

disables the

AUTO/MAN key

except from the

selected control

source.

Parameter Range:

OFF = Enable the AUTO/MAN key regardless of

control source

ON = Disable the AUTO/MAN key except from the

selected control source

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters:

P.000 Control Source

P.053 Manual Reference Preset Enable

Table 4.6 – AUTO/MAN Key Status Based on P.000 and P.052

Control Source (P.000 =)

P.052

Front Panel

AUTO/MAN Key

OIM/CS3000

AUTO/MAN Key

Front panel (LOCL)

OFF

Active

Inactive

Terminal strip (rE)

OFF

Active

Active

Network/option board (OP)

OFF

Active

Active

OIM/CS3000 (SErL)

OFF

Inactive

Active

Front panel (LOCL)

ON

Active

Inactive

Terminal strip (rE)

ON

Inactive

Inactive

Network/option board (OP)

ON

Inactive

Inactive

OIM/CS3000 (SErL)

ON

Inactive

Active