With DC braking enabled (H.005 = ON), braking will be activated after a stop

command when the decelerating drive reaches a speed corresponding to DC Braking

Start Frequency (H.006). The braking period ends after the programmed time

regardless of the actual motor speed. The value should be set to a level that avoids

activation at rest.

Operating a motor continuously at a particular frequency may cause vibrational

resonance within some machines. Three independent parameter pairs can be

configured for avoidance frequency and frequency band to prevent motor vibration by

preventing the drive output frequency from operating within the selected band(s).

Refer to figure 4.12.

The actual avoidance frequency selection is limited by Minimum Speed (P.003) and

Maximum Speed (P.004). Normal acceleration and deceleration is not affected by this

function.

H.008 DC Braking Time

This parameter sets

the time period for

which DC braking will

be applied.

Parameter Range:

0.1 to 20.0 seconds

Default Setting:

3.0

Parameter Type:

Tunable

Refer also to parameters:

H.005 DC Braking Enable

H.006 DC Braking Start Frequency

H.007 DC Braking Current

H.009 Avoidance Frequency Enable

This parameter

enables the

avoidance frequency

bands selected in

H.011, H.013, and

H.015.

Parameter Range:

OFF = Disable avoidance frequency processing
ON = Enable avoidance frequency processing

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters:

P.003 Minimum Speed

P.004 Maximum Speed

H.010 to H.015 Avoidance Frequency Midpoint and

Band 1, 2, and 3