GV3000/SE AC Drive Software Reference, Version 6.06

Losses compensation is the scaled output of the speed loop S/Ramp block (speed

reference). It is added to the speed loop output and the inertia compensation signal to

produce the final torque reference.

Refer to the speed loop block diagram in Appendix H.

For SVC operation, in the absence of a speed feedback device, operation of the speed

loop is based on an estimated speed feedback. Estimated speed feedback is based

on knowing the slip of the motor, which changes with motor temperature. This

parameter is provided to accommodate various operating conditions.

For a cold motor, the typical value should be 0.80. For a hot motor, the value should be

1.0.

U.028 Losses Compensation Gain

This parameter

specifies the gain

applied to the speed

loop reference signal

to generate the

losses compensation

signal. The result is

added to the speed

PI output to produce

the torque reference

signal.

Parameter Range:

0.0 to 1.000

Default Setting:

0.0 (Disable losses compensation)

Parameter Type:

Tunable

Refer also to parameters:

U.026 Current Compounding Gain

U.027 Inertia Compensation Gain

U.030 SVC Slip Adjust

This parameter

adjusts the slip

compensation to

match the operating

temperature of the

motor.

This feature applies

to SVC operation

only.

Parameter Range:

0.50 to 1.50

Default Setting:

1.00

Parameter Type:

Tunable

Refer also to parameters:

N/A