P.008 Terminal Strip Speed Reference Source

(continued)

= Selection combination is acceptable.

If an optional RMI board is installed in the drive, refer to Appendix F for more

information regarding digital input configuration.

For more information about the analog input, refer to Appendix G.

Table 4.3 – Acceptable P.007 and P.008 Selection Combinations

P.007

Selections

P.008 Selections

0

1

2

3

4

5

6

7

0

1

2

3

4

5

6

7

8

9

10

11

12

P.007/P.008 Selection Example

If you want to select the MOP as the speed reference source, P.008 must be set to 1.

Next, select the value for P.007 using table 4.3. Following the 1 column down under

P.008 Selections, the acceptable selections for P.007 are 4, 5, 6, 7, or 12.

P.009 Terminal Strip Analog Input Offset

This parameter

allows for correcting

any offset in the

terminal strip analog

input prior to the

signal reaching the

drive.

This parameter is not

used if the terminal

strip analog input is

used as vector torque

reference

(U.000 = 1).

Parameter Range:

-900 to +900

*

Default Setting:

0

Parameter Type:

Tunable

Refer also to parameters:

P.000 Control Source

*

For 0 to 10 V (or -10 V to +10 V input), a value of +1 equals an offset of approximately 10 mV.

For 0 to 20 mA input, a value of +1 equals an offset of approximately 20

µA.