GV3000/SE AC Drive Software Reference, Version 6.06

P.028 Speed Display Scaling

(continued)

For V/Hz regulation, P.028 will correspond to H.001:

Actual Speed in Hz x P.028 = value displayed when SPEED monitor mode

H.001 or selected reference is selected

Note that the values entered for P.003 and P.004 are automatically converted to P.028

units by the system. Therefore, the adjustment range for the manual reference is

limited as follows:

For vector regulation:

Minimum reference = P.003 x P.028 Maximum reference = P.004 x P.028

U.017

U.017

For V/Hz regulation:

Minimum reference = P.003 x P.028 Maximum reference = P.004 x P.028

H.001

H.001

Important: This parameter does not change the speed. It changes only the scaling

value applied to the display.

V/Hz Speed Display Scaling Example

Your application requires the display to be scaled to show the speed reference or

the output speed as 800 gallons/minute when operating at maximum speed.

H.001 (Motor Nameplate Base Frequency) = 60
Step 1. Set parameter P.028 = 800
Step 2. Enter SPEED monitor mode by pressing the PROGRAM key until the

PROGRAM LED turns off and the SPEED LED turns on.

Step 3. Start the drive (press the START key).
Step 4. When the drive is running at half of rated speed, the display shows that

speed is 400 (gallons/minute).

Using the equation for V/Hz regulation: 30 x 800 = 400

60