Programming Reference

4-37

If DC bus voltage drops below the low DC bus voltage threshold for more than the time

set in P.042, fault code LU is logged. After line voltage has been restored, the fault

must be reset, and then the drive may be restarted.

If line voltage is restored before the specified time is exceeded, the drive will

accelerate to operating speed at the rate specified in P.001 (Accel Time 1).

For V/Hz regulation, alarm code LIL will flash on the display during a line dip

ride-through. The levels for LIL and LU depend on the parameter setting for AC Line

Voltage (H.021).

Important: The drive will restart after a reset if the start input is still asserted.

If the auto reset feature is enabled (P.043

≠ 0), faults detected while the drive is

running are logged and reset. The drive will then wait the amount of time specified in

P.044 (Fault Auto Reset Time) and, if the start input is asserted from the selected

control source, start the drive automatically. Note that the drive must run for at least

five minutes in order to reset the number of fault reset attempts to the value in P.043.

If the fault occurs again, the drive will wait and try to re-start up to the programmed

number of attempts. If the drive faults on all of these attempts, it will remain in the

faulted state and will display the fault code on the keypad/display.

P.042 Line Dip Ride-Through Time

For V/Hz regulation,

this parameter sets

the maximum time

allowed for the drive

to stay active during

low line voltage or

line voltage loss.

For vector regulation,

this value is fixed at

500 ms.

Parameter Range:

0.1 to 999.9 seconds (V/Hz)
500 ms (vector)

Default Setting:

5.0

Parameter Type:

Configurable

Refer also to parameters:

H.017 Input Power/Snubber Configuration

H.021 AC Line Voltage

U.018 AC LIne Voltage

P.043 Fault Auto Reset Attempts

This parameter

selects the number of

times the drive will

attempt to reset drive

faults.

Parameter Range:

0 to 10

Default Setting:

0

Parameter Type:

Configurable

Refer also to parameters:

P.044 Fault Auto Reset Time